54 --
MI00/10056 rev. 8 —05/2006
The measurement signals are accessed from the load output - reserve supply page as follows:
LOAD/RES ALARMS
NO ALARMS ACTIVE
Normal operating mode
press once
LOAD f xx.x Hz
A xxx V B xxx V C xxx V
Displays the frequency and phase-neutral voltage
supplied to the load.
press once
LOAD f xx.x Hz
AB xxx V BC xxx V CA xxx V
Displays the frequency and phase-phase voltage
supplied to the load.
press once
LOAD
A xxx A B xxx A C xxx A
Displays the current supplied to the load.
press once
LOAD
A x% B x% C x%
Displays the load capacity percentage of the UPS rated
value.
press once
LOAD P.F. 0.99
P = 80kW s = 80kVA
Displays the Peak Factor of the load current.
press once
RESERVE F xx.xHz
A xxx V B xxx V Cxxx V
Displays the frequency and phase-neutral voltage
supplied to the reserve line.
press once
RESERVE F xx.xHz
AB xxx V BC xxx V CA xxx V
Displays the frequency and phase-phase voltage
supplied to the reserve line.